What is the power rating of this Siemens SINAMICS Power Module?
The Siemens SINAMICS Power Module has a rated power of 4.00 kW under Low Overload (LO) conditions and 3.00 kW under High Overload (HO) conditions.
What is the input and output voltage range of this power module?
The input line voltage for this power module ranges from 380 to 480 V ±10 %. The output rated voltage is 400V according to IEC standards and 480V according to NEC standards.
What is the frequency range of this power module?
The line frequency of the Siemens SINAMICS Power Module ranges from 47 to 63 Hz. The output frequency for vector control is 0 to 200 Hz and for V/f control is 0 to 550 Hz.
What are the dimensions of the Siemens SINAMICS Power Module?
The dimensions of the Siemens SINAMICS Power Module are 292 mm in height, 100 mm in width, and 165 mm in depth.
What is the overload capability of this power module?
Under Low Overload (LO) conditions, the Siemens SINAMICS Power Module can handle 1.1 times the rated output current for 57 seconds with a cycle time of 300 seconds. Under High Overload (HO) conditions, it can handle 1.5 times the output current rating for 57 seconds with a cycle time of 300 seconds.
What is the cooling requirement for this power module?
The Siemens SINAMICS Power Module requires internal air cooling. The cooling air requirement is 0.009 m³/s.
What is the sound pressure level of this power module?
The sound pressure level of the Siemens SINAMICS Power Module is 72 dB at a distance of 1 meter.
What is the efficiency of this power module?
The efficiency of the Siemens SINAMICS Power Module is 0.97.
What is the weight of this power module?
The Siemens SINAMICS Power Module weighs 3.10 kg.
What is the degree of protection provided by this power module?
The Siemens SINAMICS Power Module has a degree of protection of IP20 / UL open type.