What is the main function of this bus controller module?
The X20BC0063 bus controller module is designed to connect X2X Link I/O nodes to PROFIBUS DP, supporting all its options and additional properties. It enables cyclic and non-cyclic data transfer and provides device, module, and channel diagnostics according to the PROFIBUS DP standard.
What is the maximum transfer rate supported by this module?
The X20BC0063 supports a maximum transfer rate of 12 Mbit/s on the PROFIBUS DP interface.
Does this module have automatic transfer rate detection?
Yes, the X20BC0063 bus controller module features automatic transfer rate detection for the PROFIBUS DP interface.
What is the operating temperature range for this module?
The X20BC0063 module has an operating temperature range of -25 to 60°C for horizontal installation and -25 to 50°C for vertical installation.
What are the required accessories for this module?
To use the X20BC0063 module, you will need to order the following accessories separately: X20TB12 terminal block, X20PS9400 or X20PS9402 power supply module, and X20BB80 bus base.
What certifications does this module have?
The X20BC0063 module has CE, KC, UL cULus E115267, Industrial control equipment HazLoc cCSAus 244665, Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc, IP20, Ta = 0 - Max. 60°CFTZÚ 09 ATEX 0083X, and GOST-R certifications.
What is the IP rating of this module?
The X20BC0063 bus controller module has an IP20 rating according to EN 60529.
How do I set the PROFIBUS DP node number for this module?
The PROFIBUS DP node number for the X20BC0063 module can be configured using the two number switches on the module. The valid node numbers range from 1 to 125.