What is the main application of this motor circuit breaker?
The main application of the GV2P14 motor circuit breaker is motor protection.
What is the trip unit technology used in this motor circuit breaker?
The GV2P14 motor circuit breaker uses thermal-magnetic trip unit technology.
What is the rated current of this motor circuit breaker?
The rated current of the GV2P14 motor circuit breaker is 10A.
What is the thermal protection adjustment range for this motor circuit breaker?
The thermal protection adjustment range for the GV2P14 motor circuit breaker is 6 to 10A.
What is the breaking capacity of this motor circuit breaker?
The breaking capacity of the GV2P14 motor circuit breaker varies depending on the voltage. For example, it has a breaking capacity of 100 kA Icu at 230/240 V AC 50/60 Hz and 6 kA Icu at 690 V AC 50/60 Hz.
What is the control type of this motor circuit breaker?
The GV2P14 motor circuit breaker has a rotary handle control type.
What are the dimensions of this motor circuit breaker?
The dimensions of the GV2P14 motor circuit breaker are 45mm in width, 89mm in height, and 97mm in depth.
What is the IP degree of protection for this motor circuit breaker?
The GV2P14 motor circuit breaker has an IP20 degree of protection conforming to IEC 60529.
What is the operating altitude for this motor circuit breaker?
The GV2P14 motor circuit breaker can operate at an altitude of up to 2000 meters.
Is this motor circuit breaker RoHS compliant?
Yes, the GV2P14 motor circuit breaker is RoHS compliant.