What is the description of this part?
This part is a TeSys D LC1D Contactor, with a 24 V dc Coil, 3 Pole, 18 A, 7.5 kW, 3NO.
What is the utilisation category of this part?
The utilisation category of this part is AC-4, AC-1, AC-3, AC-3e.
What is the rated operational voltage of this part?
The rated operational voltage for the power circuit is <= 690 V AC 25...400 Hz and <= 300 V DC.
What is the control circuit voltage of this part?
The control circuit voltage of this part is 24 V DC.
What is the motor power of this part?
The motor power of this part is 4 KW at 220...230 V AC 50/60 Hz (AC-3), 7.5 KW at 380...400 V AC 50/60 Hz (AC-3), 9 KW at 415...440 V AC 50/60 Hz (AC-3), 10 KW at 500 V AC 50/60 Hz (AC-3), and 10 KW at 660...690 V AC 50/60 Hz (AC-3).
What is the maximum horse power rating of this part?
The maximum horse power rating of this part is 1 Hp at 115 V at AC 50/60 Hz for 1 phase, 3 Hp at 230/240 V at AC 50/60 Hz for 1 phase, 5 Hp at 200/208 V at AC 50/60 Hz for 3 phase, 5 Hp at 230/240 V at AC 50/60 Hz for 3 phase, 10 Hp at 460/480 V at AC 50/60 Hz for 3 phase, and 15 hp at 575/600 V at AC 50/60 Hz for 3 phase.
What is the pole contact composition of this part?
The pole contact composition of this part is 3 NO.
What is the rated breaking capacity of this part?
The rated breaking capacity of this part is 300 A at 440 V power circuit according to IEC 60947.
What is the conventional free air thermal current of this part?
The conventional free air thermal current of this part is 10 A at 140 °F (60 °C) for the signalling circuit and 32 A at 140 °F (60 °C) for the power circuit.